Xylo engineered hardwood is generally suitable for use with waterborne underfloor heating. Specific precautions keep the floor stable over its life.

Screed
Below 2.0% MC
Humidity
Below 70% RH
Surface max
25°C
Change rate
1°C per day
Before installation

Commissioning and moisture

Inadequate screed drying is the single most common cause of failure: it shows up as surface discolouration, a cloudy or opaque finish on lacquered boards, distortion, buckling or excessive expansion.

01Screed

Moisture and humidity limits

At the time of installation, the screed moisture content needs to be below 2.0% MC, or alternatively the ambient relative humidity needs to be below 70% RH.

02Commission

Run the system first, then turn it off

  • The underfloor heating system must be fully operational at least two weeks prior to installation, to allow the subfloor to dry and stabilise
  • The system should be switched off 2–3 days before the flooring is laid
  • The underfloor heating must remain off for 48 hours after installation
03Heat

How the heat is distributed

The heating system must distribute heat evenly across the subfloor. Localised “hot spots” can damage the flooring and impair performance.

The maximum surface temperature recommended for Xylo Flooring is 25°C, allowing for the thermal sensitivity of certain wood species.

Avoid excessively humid or excessively dry conditions, as either can create internal stress within the boards and affect dimensional stability.

04Fixing

Installation approach

Professional opinions vary on the best installation method over underfloor heating. In larger areas, fixing the flooring to the subfloor using a flexible adhesive can help reduce potential movement and improve dimensional stability.

This method may provide additional performance benefits depending on site conditions and installer preference.

Living with it

Running the system

A floor laid correctly can still be damaged by how the heating is operated afterwards. Gradual is the whole principle.

01Climate

Indoor humidity through the year

The recommended indoor climate for engineered hardwood flooring is 45%–65% relative humidity, which can be monitored with an inexpensive hygrometer.

During summer, RH levels of around 70% are generally acceptable. Winter poses the greater risk: levels may fall as low as 30%, creating an overly dry environment and causing excessive contraction of the boards. Static shocks are a common indicator that indoor RH is too low.

To maintain healthy humidity through winter, consider using a humidifier; even pot plants help contribute moisture to the air.

02Gradual

Never switch it on suddenly

Temperature adjustments must be made gradually to avoid thermal shock.

  • Increase or decrease temperature at a rate of no more than 1°C per day
  • Set the system low early in the season, then bring it up steadily
  • Maintain a consistent temperature through the winter rather than frequently turning the heating on and off

Ideal comfort — and optimum conditions for the flooring — typically falls between 16°C and 21°C.

03Ranges

Which floors suit it

Many Xylo floors are suitable for use with underfloor heating. Our SPC ranges suit most water-based systems but not electric ones, and the Battersea laminate collection is rated for underfloor heating throughout.

If in doubt, consult your underfloor heating supplier for compatibility, and ask us for the data sheet covering the range you are specifying.